RCD & RCBO Selection Guide

Review residual-current type and sensitivity, then compare circuit current, cable capacity, voltage and fault duty with entered RCD or RCBO ratings.

Application example · Illustrative inputs

Reviewing a single-phase branch with PXB6L-63 data

For a 230 V branch with an assumed 18 A load and 25 A corrected cable capacity, compare a 20 A device against Ib ≤ In ≤ Iz. If the equipment requirements call for Type A and 30 mA, the CHAC PXB6L-63 page lists those options, together with 230 V for 1P+N/2P and 6 kA Ics. Entering a 4.5 kA fault level clears the guide’s numeric fault comparison, subject to the applicable rating and standard. Confirm the exact variant, leakage conditions and neutral arrangement; the calculator records the required type rather than determining it from load current.

Product data: PXB6L-63 Electromagnetic Residual Current Operated Circuit Breaker