Circuit Breaker Size Calculator
Calculate a reference circuit breaker size from load power, voltage, power factor and a sizing factor. Compare the result with MCB and MCCB product ratings.
A first current-rating check for an MCB or MCCB. Cable protection and breaking capacity need separate checks.
Result
Reference breaker rating
20APreliminary calculationI = P × 1,000 / (√3 × V × PF); In = next rating ≥ I × factorGeneric current series up to 1,600 A. Verify actual product availability, cable ampacity, trip curve, fault breaking capacity and local rules. No CHAC model is selected.
Why this result?
Formula and method
Calculate a reference circuit breaker size from load power, voltage, power factor and a sizing factor. Compare the result with MCB and MCCB product ratings.
How to use this calculator
- Enter the real electrical load power, voltage and circuit type.
- For AC, enter the known power factor.
- Use a sizing factor justified by project requirements, then verify the reference against actual equipment.
Calculation limits
A universal 1.25 factor is not assumed. This calculation does not establish breaking capacity, selectivity, cable protection or code compliance.
How to size a breaker from load current
A breaker’s current rating and short-circuit breaking capacity describe different duties. This tool calculates the operating current, applies your sizing factor and rounds up within a generic current-rating series. It does not assess the available fault current.
Input notes
| Input | What to check |
|---|---|
| Load power | Enter electrical input kW. Motor shaft output needs a separate efficiency calculation before it can represent input power. |
| Sizing factor | The default 1.00 leaves current unchanged. Use another value only where the applicable installation rules and equipment duty justify it. |
| Reference rating | The next listed ampere rating is a starting point. Availability, frame sizes and adjustable trip settings vary by product series. |
Worked example · initial form values
Reference rating for an 11 kW load
Three-phase · 400 V · PF 0.85 · sizing factor 1.00
Load current = 11,000 / (√3 × 400 × 0.85) = 18.68 A
Factored current = 18.68 × 1.00 = 18.68 A
Next rating in the tool’s series = 20 A
20 A
The result clears the entered current check. It does not establish that a 20 A device protects the cable or has adequate breaking capacity.
Checks that still determine the breaker
- Confirm the cable’s corrected current-carrying capacity and the protective device’s overload characteristics. Rounding up must not leave the conductor inadequately protected.
- Check AC or DC voltage, pole arrangement, trip curve or settings, prospective fault current, breaking capacity and upstream coordination against the exact CHAC model data.
Frequently asked questions
Does this result identify a CHAC breaker model?
No. It is a reference current rating. Confirm the applicable CHAC product series, voltage, poles, breaking capacity, trip characteristics, cable protection and installation requirements.
Should every breaker be sized at 125% of the load?
No universal multiplier is built into this tool. Continuous-load provisions, equipment ratings and installation rules differ. Apply a factor supported by the requirements for the actual circuit.
Is a 20 A breaker’s breaking capacity 20 A?
No. 20 A describes its rated current. Short-circuit breaking capacity is a separate rating, commonly expressed in kA, at a specified voltage and under a stated product standard.
Can I select a motor breaker from running current alone?
Running current is only one input. Starting duty, overload protection, motor nameplate data and coordination with the contactor and short-circuit protective device also matter.
Need help choosing a CHAC product?
Send the system voltage, load current, and installation conditions with your inquiry.
Application example · Illustrative inputs
From a machine’s running current to an available breaker rating
Consider a machine feeder drawing 7.5 kW of electrical input at 400 V three-phase and power factor 0.85. With the sizing factor left at 1.00, the operating current is 12.74 A and the calculator returns a 13 A generic reference. The CHAC PXB6-63 product table does not list 13 A; its next higher listed option is 16 A. This is where calculation and product selection differ. A 16 A variant can only be considered after checking cable protection, inrush and the applicable trip curve. The published 6 kA Icu = Ics is a separate fault-duty check.