Power Factor Correction Calculator

Estimate capacitor-bank compensation in kvar from active power and existing and target power factors. Includes the power factor correction formula and example.

Application example · Illustrative inputs

Estimating compensation for a commercial distribution load

For a stable 75 kW load with lagging power factor 0.78, entering a target of 0.95 gives a compensation estimate of 35.52 kvar. That figure is useful when discussing the size of a compensation study, rather than ordering a capacitor bank directly. CHAC CQM6 and CQW2 product data can support the associated distribution-protection review, but the kvar result does not select either breaker. Harmonics, switching steps, inrush and capacitor duty still need assessment. An ordinary AC-3 motor contactor must not be assumed suitable for switching the proposed capacitor bank.