Power Factor Correction Calculator
Estimate capacitor-bank compensation in kvar from active power and existing and target power factors. Includes the power factor correction formula and example.
Estimate compensation for a stable lagging load. Harmonics and capacitor duty need separate checks.
Result
Compensation estimate
55.32kvarPreliminary calculationQc = P × [tan(acos PF₁) − tan(acos PF₂)]Assumes lagging displacement power factor and a stable load. Harmonics, resonance, switching steps and overcompensation require specialist checks.
Why this result?
Formula and method
Estimate capacitor-bank compensation in kvar from active power and existing and target power factors. Includes the power factor correction formula and example.
How to use this calculator
- Enter the load’s measured active power.
- Enter its existing lagging power factor.
- Choose a target no lower than the existing value.
Calculation limits
This is not a harmonic or capacitor-duty assessment. It does not specify capacitor voltage, detuning reactors, switching equipment or a product model.
Power factor correction calculations for capacitor-bank kvar
For a stable lagging load, capacitor compensation reduces the reactive power supplied upstream. Active power stays the same in this calculation. The required kvar is the difference between the reactive power at the existing displacement power factor and at the target.
Input notes
| Input | What to check |
|---|---|
| Active power | Use the measured kW for the load and operating condition to be corrected. Installed nameplate totals may not represent the running load. |
| Existing PF | The formula assumes lagging displacement power factor. True power factor affected by harmonics is not interchangeable with displacement PF. |
| Target PF | Choose a value no lower than the existing PF and check utility requirements. The result does not specify an automatic-bank step arrangement. |
Worked example · initial form values
Correcting a 100 kW load from 0.75 to 0.95
100 kW active power · existing lagging PF 0.75 · target PF 0.95
Q before = 100 × tan(acos 0.75) = 88.19 kvar
Q after = 100 × tan(acos 0.95) = 32.87 kvar
Qc = Q before − Q after = 55.32 kvar
55.32 kvar
The theoretical compensation is 55.32 kvar. Actual bank ratings and stages need to suit voltage, changing load and harmonic conditions; this is not a capacitor-bank specification.
Before specifying a capacitor bank
- Measure load variation and harmonic conditions. Capacitors can interact with system inductance; detuned reactors and switching arrangements need a separate design review.
- Avoid excess compensation at light load. Check capacitor voltage and current duty, inrush, discharge provisions, switching equipment and protection rather than selecting a bank on kvar alone.
Frequently asked questions
Can this value specify a capacitor bank directly?
No. It gives a reactive-power estimate for a stable lagging load. Harmonics, resonance, switching stages, voltage rating and overcompensation require additional engineering checks.
Will power factor correction reduce my load’s kW by the same percentage?
No. The model keeps useful active power unchanged while reducing upstream reactive power, apparent power and current. Billing effects depend on the tariff; lower current can also reduce distribution losses.
Why not always target a power factor of 1.00?
A varying load can become overcompensated when fixed capacitance remains connected. Choose a target and control arrangement appropriate to the load and utility requirements.
Can ordinary capacitors correct harmonic distortion?
This displacement-PF equation does not calculate harmonic mitigation. Harmonic measurements and a resonance assessment are needed before selecting capacitors, reactors or filters.
Need help choosing a CHAC product?
Send the system voltage, load current, and installation conditions with your inquiry.
Application example · Illustrative inputs
Estimating compensation for a commercial distribution load
For a stable 75 kW load with lagging power factor 0.78, entering a target of 0.95 gives a compensation estimate of 35.52 kvar. That figure is useful when discussing the size of a compensation study, rather than ordering a capacitor bank directly. CHAC CQM6 and CQW2 product data can support the associated distribution-protection review, but the kvar result does not select either breaker. Harmonics, switching steps, inrush and capacitor duty still need assessment. An ordinary AC-3 motor contactor must not be assumed suitable for switching the proposed capacitor bank.
Product data: CQM6 Standard Molded Case Circuit Breaker (MCCB) OEM Manufacturer · CQW2 Series Air Circuit Breaker


