CQBD-63 Small DC circuit breaker

The CHAC CQBD-63 DC circuit breaker offers overload and short-circuit protection with a non-polar design and contact-position indication. One- to four-pole versions cover DC voltages from 300V to 1200V; match the pole arrangement and tripping characteristic to the circuit.

Poles:
1P / 2P / 3P / 4P
Rated Current:
1 / 2 / 3 / 4 / 6 / 10 / 16 / 20 / 25 / 32 / 40 / 50 / 63A
Rated Voltage:
300V DC (1P); 600V DC (2P); 900V DC (3P); 1200V DC (4P)
Breaking Capacity:
10kA Icu / 7.5kA Ics (technical-table rating)
Tripping Curve:
B (4–7In); C (8In ±20%); D (12In ±20%)
Standard:
IEC 60947-2 / GB/T 14048.2
Customization:
One-Stop OEM/ODM Service

Product Overview

The CHAC CQBD-63 non-polar DC circuit breaker combines overload and short-circuit protection with contact-position indication. One- to four-pole configurations cover different DC voltages, making the pole arrangement part of the electrical specification rather than a space-only choice.

For importers, distributors and equipment manufacturers, CHAC can review the requested configuration against the circuit requirements and destination-market documents. Agree the exact model, drawings and marking requirements before sample approval or a repeat order.

Key Selection Points

  • Poles and operating voltage: 1P 300V; 2P 600V; 3P 900V; 4P 1200V DC. Select the pole arrangement and approved connection together.
  • Rated current: 1–63A in the listed steps. Coordinate the selected rating with design current, cable ampacity and environmental conditions.
  • Short-circuit ratings: Technical-table configuration: Icu 10kA; Ics 7.5kA. Confirm the ordered breaking-capacity version; other variants must have their own verified ratings.
  • Trip characteristic: B: 4–7In; C: 8In ±20%; D: 12In ±20%. Use these model-specific DC thresholds, not generic AC MCB curve values.

Typical Applications

Consider CQBD-63 for DC distribution and PV assemblies where the selected voltage, fault-current rating and trip characteristic meet the project design. Non-polar construction does not remove the need to follow the model wiring diagram.

Applications and Selection Guide

Selection item CQBD-63 configuration What to verify
Poles and operating voltage 1P 300V; 2P 600V; 3P 900V; 4P 1200V DC Select the pole arrangement and approved connection together.
Rated current 1–63A in the listed steps Coordinate the selected rating with design current, cable ampacity and environmental conditions.
Short-circuit ratings Technical-table configuration: Icu 10kA; Ics 7.5kA Confirm the ordered breaking-capacity version; other variants must have their own verified ratings.
Trip characteristic B: 4–7In; C: 8In ±20%; D: 12In ±20% Use these model-specific DC thresholds, not generic AC MCB curve values.

Use these checks to compare the protection function, configuration and related CHAC products before specifying CQBD-63. Related products are selection alternatives or system components, not automatic replacements.

Compare PXB6DC-63M for the required function

The CHAC PXB6DC-63M DC miniature circuit breaker offers overcurrent protection across a 0.5–63A rated-current range. Available in one to four poles, its voltage rating rises from 125V DC for 1P to 500V DC for 4P; use the specified pole arrangement and model-specific tripping characteristics.

Related ProductSystem DesignVerify Compatibility

Compare CQHD for the required function

The CHAC CQHD PV DC combiner box combines photovoltaic string inputs with DC circuit-breaker protection. Choose from six input/output configurations to match your PV array layout, and confirm the voltage and current ratings for the selected model.

Related ProductSystem DesignVerify Compatibility

Need Help Specifying CQBD-63?

Send the circuit requirements, selected configuration, destination market and quantity for a model-specific review.

Request a Quote

Keep the voltage-to-pole relationship in the purchase order

The CQBD-63 voltage rating rises with the documented pole arrangement. State both the required DC voltage and number of poles when requesting a quotation, and obtain the corresponding connection diagram before panel layout approval.

Use the CQBD-63 curve data for protection checks

The B/C/D letters on this DC model do not carry the same numerical thresholds as a typical AC MCB. Check the published characteristic against load inrush and the minimum fault current, then confirm the ordered current and breaking-capacity variant.

How to Specify a CQBD-63 Order

Use the configuration details below in the purchase specification. Keep the approved drawing revision and product identification with the order so repeat deliveries can be checked consistently.

Order detail Information to include
Poles and operating voltage 1P 300V; 2P 600V; 3P 900V; 4P 1200V DC — Select the pole arrangement and approved connection together.
Rated current 1–63A in the listed steps — Coordinate the selected rating with design current, cable ampacity and environmental conditions.
Short-circuit ratings Technical-table configuration: Icu 10kA; Ics 7.5kA — Confirm the ordered breaking-capacity version; other variants must have their own verified ratings.
Trip characteristic B: 4–7In; C: 8In ±20%; D: 12In ±20% — Use these model-specific DC thresholds, not generic AC MCB curve values.
Project and documents Supply the application, installation conditions and destination-market document requirements.
Quantity and identification State the quantity, sample requirement, packaging language and any proposed branding; confirm feasibility before approval.

Check Installation Fit Before Approval

  • Use the CQBD-63 dimension drawing to verify mounting, terminal access, operating clearance and conductor bending space.
  • Confirm conductor preparation, terminal compatibility and tightening instructions for the exact configuration. A conductor reference table does not replace project cable sizing.
  • Review temperature, enclosure conditions and the protective arrangement with the equipment designer. Do not infer compatibility from a similar model name.
  • Have qualified personnel install and verify the equipment using the model instructions and applicable isolation and testing procedures.

Product description

Project Parameter
Rated Shell Current 63A
Meet The Standard GB/T 14048.2,IEC 60947-2
Rated Insulation Voltage Ui 1200V
Rated Impulse Withstand Voltage Uimp 6kV
Rated Current 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A
Rated Voltage DC300V(1P),600V(2P),900V(3P),1200V(4P)
Release Curve B(4In-7In),C:8In±20%,D:12In±20%
Polar Number 1P,2P,3P,4P
Unipolar Width 18mm
Ultimate Short-circuit Breaking Capacity Icu 10kA
Operating Short-circuit Breaking Capacity Ics 7.5kA
Reference Temperature 30℃
Usage Category A
Mechanical Life 20000 times
Electrical Life More than 1500 times
Protection Level IP20
Wiring Capacity (mm2) 16
Wiring Method Both up and down incoming lines are acceptable

Product release characteristics

Rated current (A) Overload tripping characteristic Instantaneous release characteristic (A)
1.05ln agreed non trip time H (cold state) 1.30ln agreed release time H (hot state)
ln ≤ 63 1 1 B(4ln-7ln) C:8ln±20%,D:12ln±20%

Model meaning

Time-current characteristics

Product appearance and installation dimensions

Why Choose CHAC

CHAC Electric supplies electrical protection and control products for importers, distributors and equipment brands. For CQBD-63, agree the configuration, technical documents, approved sample and identification requirements before production. The company facilities shown below provide company context, not a claim that every model uses the same production or test process.

01

CONFIRM THE SPECIFICATION

Agree the CQBD-63 configuration, circuit duty and installation requirements.

02

REVIEW THE DOCUMENTS

Confirm model-specific drawings and destination-market requirements.

03

APPROVE THE SAMPLE

Record the accepted configuration and marking requirements.

04

DEFINE ORDER CHECKS

Agree packaging, identification and delivery requirements in the quotation.

CHAC Automated Assembly Line

Automated Assembly Line

CHAC Testing Laboratory

Testing Laboratory

CHAC Injection & Stamping

Injection & Stamping

CHAC Quality Inspection

Quality Inspection

What Can We Customize?

Discuss CQBD-63 product identification, packaging and documentation with CHAC. Each proposed change is subject to technical feasibility, marking rules and approval of the exact order; no altered rating or certification is implied.

Logo & Branding

Submit logo artwork and marking requirements for review against the available print area and mandatory product markings.

CHAC CQBD-63 product view

Packaging & Manuals

Define carton labels, packaging language, product identification and instruction requirements for the destination market.

CHAC CQBD-63 product view

Configuration Selection

Specify CQBD-63 with the required poles and operating voltage, operating conditions and protection duty. Confirm the complete order combination.

CHAC CQBD-63 product view

Assembly Requirements

Provide the mounting and connection requirements for review. Changes to the housing, terminals or operating arrangement require engineering approval.

CHAC CQBD-63 product view

Market Documentation

Request documents covering the exact CQBD-63 model and destination market. A standard reference alone is not evidence of certification.

CHAC CQBD-63 product view

Sample Approval

Agree the sample specification, drawing revision and acceptance criteria before confirming a production order.

CHAC CQBD-63 product view

Technical Documents and Support

DOC

CQBD-63 Technical Documents

Request the CQBD-63 datasheet, configuration drawing, installation instructions and available model-specific market documents.Request Datasheet

SUP

Need Technical Documents?

Send the application, electrical requirements, assembly layout and destination market for configuration and document review.Contact Us

CQBD-63 Product FAQ

Does polarity matter on a DC circuit breaker?

It depends on the breaker design. CQBD-63 is specified as non-polar, but its voltage, pole arrangement and wiring instructions still apply. Do not transfer this characteristic to another DC model without confirmation.

Can a one-pole CQBD-63 be used at 1200V DC?

No. The table assigns 300V DC to 1P and 1200V DC to 4P, with 600V for 2P and 900V for 3P. Use the approved arrangement and wiring for the required voltage.

Are its B, C and D curves the same as AC MCB curves?

No such equivalence should be assumed. CQBD-63 specifies B at 4–7In, C at 8In ±20% and D at 12In ±20%. Use the actual characteristic for protection coordination.

How do I choose the CQBD-63 current rating?

Use circuit design current and conductor ampacity, then check inrush, ambient conditions and the fault-disconnection requirement. Do not increase current rating simply to stop a recurring trip without investigating its cause.

What is the difference between Icu and Ics?

Icu and Ics describe ultimate and service short-circuit interruption duties under stated test conditions. Use the CQBD-63 values for the selected voltage and configuration, and compare them with the prospective fault current.

What should I include in a CQBD-63 purchase specification?

Specify DC operating voltage, poles, rated current, the exact trip characteristic and required fault capacity. Include wiring requirements, load type, destination-market documentation, quantity and any branding request.